A plant is pumping 600 gallons per minute (GPM) of chill water through an 8” pipe into an open tank. When the pump turns off, the pump pressure is gone.  In its place, negative pressure (or a vacuum) generated by falling water in the pipe creates a siphoning effect, and the water continues to fill the tank. Without intervention, the flow will continue until the water level drops below the supply pipe inlet.

To stop the flow of falling water from generating a vacuum, that generates more flow, the plant will need to add a tee and install a vacuum breaker at the highest point in the piping.

How does a Vacuum Breaker work? 

A vacuum breaker consists of five primary components: the body, O-ring, ball, spring, and retainer tube. In normal operation, the spring aligns the ball tightly against the O-ring while positive pressure holds it securely in place, maintaining a sealed condition. When sufficient vacuum develops, the pressure differential overcomes the spring force, lifting the ball off the seat, and allowing atmospheric air to enter the system.

Vacuum breakers are available in various sizes; each designed with a specific cracking vacuum and air flow capacity based on its orifice. In addition to preventing siphoning, they play a critical role in protecting equipment by preventing the collapse of pipes and tanks, aiding in drainage where vacuum conditions could otherwise restrict or stop flow.

VB Blown Up

Which vacuum breaker size do I use?

Proper sizing of a vacuum breaker is critical to effectively dissipate vacuum conditions. Two primary factors must be considered: (1) the liquid flow rate and (2) the head pressure required to lift the liquid.

In our chilled water example, the vacuum breaker must be capable of admitting air at a volume equal to the liquid flow rate, at a pressure lower than that required to lift the water column. To determine the required air capacity, the liquid flow rate is converted to standard cubic feet per minute (scfm). Since vacuum breakers operate near atmospheric conditions, air flow can be expressed in scfm.

For example, a chilled water flow rate of 600 GPM converts to:

600 GPM ÷ 7.5 gallons per cubic foot = 80 scfm

Therefore, the vacuum breaker must be sized to admit at least 80 scfm of air to effectively prevent enough vacuum from forming to lift the water under these conditions.

Based on the performance chart, one size can meet this requirement: the 1½-inch (VB8-151).  The 1½-inch valve will pass 80 scfm at approximately 4 inHg, equivalent to about 4.5 feet of water column.

VB Chart

It is important to pass the air at a lower head pressure than the pressure it will take to lift the water to the highest point. Otherwise, you will not generate enough vacuum to bring in sufficient air through the vacuum breaker to stop the siphon drainage.

To find the maximum head, measure the distance between the high-water point in the supply and the high point where the vacuum breaker is located. Convert from feet to inches of Mercury (inHg) by multiplying feet by 0.88 inHg/ft.

For example, if the water is lifted:

  • 4 feet (4 inHg), you need the larger 1-1/2” vacuum breaker
  • 2 feet (1.77 inHg), you will need a pair of 1-1/2” vacuum breakers
  • 0 feet, you have gravity drainage, not siphon drainage, and a vacuum breaker will not stop the flow

Note that this method of sizing a vacuum breaker for siphon drainage is conservative because it is very likely that the siphon drainage will break before you reach the full replacement air flow. It is not easy to calculate the exact percentage of water flow that needs to be replaced by air flow because it will vary based on system layout and flow conditions. We do know that 100% replacement with air will always break the siphon drainage.

Vacuum Breaker Installation Tips

Install the vacuum breaker at a high point in the piping above the open tank to ensure proper operation.

The vacuum breaker has a female threaded air inlet.  A short pipe or hose with a gooseneck bend can be connected to the air inlet and routed away from pedestrian areas and sensitive equipment.

Since the vacuum breaker seals with a ball and O-ring, wear over time may lead to leakage. The air inlet line should be positioned where operators can easily observe any leakage and identify when maintenance or replacement is required. This piping also helps prevent dirt and debris from entering the valve, reducing the risk of contaminants interfering with the seal.

The other end of the vacuum breaker body has an outside diameter male thread used to mount the valve in your piping. We recommend using a standpipe with a coupling, to prevent damage to the vacuum breaker if it was installed with the cage down in the direct water flow.